DID312 SERIES
Active chilled beams with heating and cooling functions are designed for various ceiling systems. Equipped with 2-pipe or 4-pipe heat exchangers and a tray for collecting condensate in case of a temporary drop in temperature below the dew point.
Recommended for rooms up to 4.20 m high
High heating and cooling capacity with low primary conditioned air flow and low noise level
Low air speed in the service area provides a high level of comfort
Three nozzle options allow you to select the required ejection
Four options for hinged outer panel
Additional equipment and accessories
Automation kit
Versions for supply and exhaust ventilation are also available
Heat exchanger with black powder coating
Wide range of powder coating colors from the RAL CLASSIC or NCS catalogs
Description
Active chilled beams bring fresh air (primary air) into a room from a centralized ventilation system, using heat exchangers to preserve indoor air quality and also to cool and/or heat it.
Primary air enters the mixing chamber through nozzles. As a result, secondary air is drawn through the face of the beam, passing through the vertically mounted heat exchangers and into the mixing chamber. In the chamber, primary air is mixed with cooled secondary air, and then supplied horizontally through slot diffusers.
There are eight models of different lengths, each of which can be equipped with three types of nozzles. This allows you to select the desired option that optimally meets the requirements for air flow and cooling capacity with low pressure drops and low noise characteristics.
Nominal length 900, 1200, 1500, 1800, 2100, 2400, 2700, 3000 mm
Length 893 – 3000 mm
Height 210/241 mm
Width 293, 300, 312 mm
Primary air pipe, diameter 123/158 mm
Primary air flow 5 – 70 l/s or 18 – 252 m³/h
Cooling capacity Up to 1830 W
Heating capacity Up to 1240 W
Max. operating pressure, water side 6 bar
Max. working temperature 75°C
Characteristics Four types of faceplate for ejected air
Vertically mounted heat exchangers with condensate trays for low cooling water temperatures
Heat exchangers for 2-pipe and 4-pipe systems
Supply and exhaust combination available
There are three nozzle sizes to achieve the best ejection. Connecting pipelines using fittings with an outer diameter of 12 mm and a flat end.
Beam option
Connections on the side surface with external thread G½”, with mechanical seal
Supply and exhaust combination with extract air connection
Materials used
The body, front frame and plate with nozzles located on it are made of galvanized sheet steel.
Heat exchanger made of copper tubes and shaped aluminum plates.
The frame and front panel (GL,GQ) are made of aluminum profiles.
Perforated front panel (LR/LQ) made of galvanized sheet steel. The visible surface of the unit is powder coated in white (RAL 9010) or another color according to the RAL scale. On request, the heat exchanger is powder coated in black (RAL 9005), the nozzle plate is powder coated in black (RAL 9005).
① Face frame
② Primary air pipe
③ Housing
④ Heat exchanger
⑤ Hanging brackets
⑥ Cooling water connections
⑦ Nozzle plate
⑧ Hot water connections
⑨ Condensate drain pipe
⑩Hinged front panel