BBHM SERIES
Round and square ceiling swirl diffusers provide high ejection levels, suitable for high air flow rates. Ceiling swirl diffusers of the BBHM series have fixed guide vanes. Horizontal air supply is carried out in all directions. The temperature difference between the supply air and the room can range from –12 to +10 K.
Flap blade (optional) to balance air flow simplifies operation. The metering point and damper blade with flexible rod (optional) allow you to adjust the air flow when the front panel is installed. To create an attractive, holistic room design, BBHM series diffusers can also be used for exhaust ventilation.
- Standard sizes 300, 400, 500, 600, 625
- Air flow level 9 – 235 l/s or 31 – 846 m³/h
- Front panel made of galvanized sheet steel with powder coating
- For supply and extract air
- For systems with variable and constant air flow
- Suitable for all types of ceilings, also suitable for free hanging when fitted with an edge panel
- Rapid equalization of temperatures and reduction of air flow speed is achieved due to the high level of ejection
- Diffusers can provide 35-fold air exchange when arranged in a row with a minimum pitch of 0.9 m (from center to center)
- Ideal for comfort zones
Ceiling swirl diffusers in air conditioning systems create a vortex supply of air for good mixing with the room air.
Description
The air flow obtained at the outlet of the diffuser allows one to achieve high ejection values, thereby quickly reducing the flow rate and leveling out the temperature difference between the supply air and the air in the room. Ceiling swirl diffusers are used for high air flows. As a result, there is a mixing of air flows in comfort zones, with a good distribution of air jets throughout the room and a small turbulent vortex in the area where people are present.
Additional equipment and accessories
- The diffuser front panel can be painted in RAL CLASSIC colors
- Plenum box with measuring point and valve flap with flexible rod
- Standard sizes 300, 400, 500, 600, 625 mm
- Min. air flow, where ΔtZ = -6 K 9 – 28 l/s or 31 – 102 m³/h
- Max. air flow level, at LWA ≅ 50 dB(A) 70 – 235 l/s or 252 – 846 m³/h
- Temperature difference between supply air and room –12 to +10K
① Diffuser front panel
② Center connection screw
③ Static chamber
④ Jumper
⑤ Hanging bracket
⑥ Connection
Optional
⑦ Seal
⑧ Valve blade for balancing air flow
⑨ Measuring point
⑩ Green cable for closing the damper blade
⑪White cable for opening the valve door
⑫ Measuring tube
⑬ Plenum box type label